Main reasons and troubleshooting methods for pump tripping failure

21 Jun 2019Email

Causes and troubleshooting of pump trip failure:

 

A. Fault phenomenon:

Since the 125mw unit of the power plant has been put into production, the pump occasionally has a problem of tripping or tripping, and there is no signal relay to be dropped. After the failure of the switching mechanism is eliminated, the cable, the secondary circuit wiring, and the relays and their settings are normal according to the conventional method, and the restart is often successful. It is suspected that it is caused by a soft fault of the dcs system, but it will still occur when it is operated on the control panel.

 

B. Find the reason:

In order to find out the cause of this phenomenon, observe the changes of the meters in the process of closing the switch to confirm what caused it to trip. In the test, the voltmeter monitors the microcomputer trip circuit, the milliampere monitors the operation of the differential relays 1cj, 2cj, and the ammeter monitors the thermal protection loop. After the meter is connected, the feed pump is started. After a period of test, the pump once trips once, and the pointer of the milliampere meter is deflected. The other monitors do not respond. The new xjl- The 0025/31 type integrated block signal relay 1xj also acts off, indicating that it is tripped by the differential protection action.

 

C. Solution:

The differential protection action first suspects that there is a fault inside the protected device. Through routine inspection, the pump motor and its cable are normal, the differential relay is verified normally, and the current transformer polarity is connected correctly. After eliminating the cause of equipment failure and wiring error, the differential protection operates during the motor starting process, indicating that the differential current of the differential circuit exceeds the differential relay setting value during this process. There are two main reasons for the differential current difference current under normal conditions: First, the current transformer on both sides of the motor has different ratio error, and there is a small difference current, which is less than 5% of the rated current id of the motor. . Second, the difference in the secondary load of the current transformer on both sides of the head and tail will also cause the difference in the ratio, so that there is a difference current. The current transformer load difference in the differential protection circuit of the pump motor is only the difference of the length of the secondary cable, which is about 50m apart, and the power consumption of the differential relay is not more than 3va at the rated current, and the secondary load is not heavy. Check that the first and last side current transformers used for differential protection of the feed pump motor are lmzbj-10, b level 15 times rated current, ratio 600/5, capacity 40 va, fully meet the requirements of secondary load.

 

The above analysis is based on normal operating conditions, and the situation is different when the motor is started. When the motor starts, the current is very large, and the current transformers on both sides of the first and last ends may be saturated. At this time, the secondary differential current may be large due to the inconsistent magnetization characteristics of the current transformers.

According to the setting of lcd-12 differential relay of Acheng Relay Factory, the operating current setting value of relay is izd=△i1×kk×in/n=0.06×3×356/120=0.534a where: △i1—first The maximum error of the tail current transformer during normal operation, 0.04 ~ 0.06; kk - reliability coefficient, 2 ~ 3; in - motor rated current; n - current transformer ratio. Should be set at 1.0a. In the case of using the b-level transformer, the differential relay operating current is set at 1.5a, and the braking coefficient is 0.4. The differential protection will occasionally operate when the motor starts, because the b-level current transformer magnetization characteristic saturation point. Lower, low saturation resistance, can not meet the requirements of differential relays.

Generally, the current transformer of the differential protection circuit is required to adopt d-stage, and the saturation point of the d-stage transformer is higher, which is not so easy to be saturated, and can reduce the differential current flowing through the differential circuit when the motor starts. When the current transformer of the d-class is replaced, the operating current of the differential relay is set at 1.0a, and the braking coefficient is 0.4, and there is no fault that the switch is tripped when the switch is closed.

Related Pump Knowledge
More Pump Knowledge
11 May 2024
The role of boiler feed pump in thermal power plant          In the operation of thermal power plant, boiler feed pump plays a crucial role. Its core...
Read more
04 May 2024
           There is a close relationship between the flow, head and efficiency of the pump, which together determine the...
Read more
27 Apr 2024
            When the O-ring of the multistage pump is damaged or aged, it needs to be replaced in time to ensure the nor...
Read more
20 Apr 2024
           Multistage centrifugal pump vs single-stage centrifugal pump: Which is more efficient? For this problem, the centrifugal pump professional ...
Read more
Related Products
More
Split Case Pump
Split Case Pump
  • Capacity:60-33005m³/h
  • Head:0.95-30.2bar
  • Price:$2200-215000
Double Suction Pump
Double Suction Pump
  • Capacity:60-33005m³/h
  • Head:0.95-30.2bar
  • Price:$2200-215000
Single Stage Chemical Pump
Single Stage Chemical Pump
  • Capacity:5.5-2600m³/h
  • Head:1.6-25bar
  • Price:$4300-37000
End Suction Chemical Pump
End Suction Chemical Pump
  • Capacity:5.5~400m³/h
  • Head:0.42-12.5bar
  • Price:$560-9800
Need More Information?
Contact us for more details about our pump, solutions and services.
Contact ZB
Tel
0086 731 88192011
Leave a message
Name*
Tel
Email*
Area
Products
Split Case Pump
Metallurgy
Mining Industry
Urban Water Supply
Petrochemical
Light Industry
Electricity
Chemical Industry
Farmland Irrigation
Other
Provide your comments and questions.